摘要:霍尼韋爾減壓閥D06F-1/2A|D06F-1/2B|D06F-3/4A|D06F-3/4B|D06F-1A|D06F-1B|D06F-11/4A|D06F-11/4B|D06F-11/2A|D06F-11/2B|D06F-2A|D06F-2B|D06FH-1/2B|D06FH-3/4B|D06FH-1B|D06FH-11/4B|D06FH-11/2B|D06FH-2B|D06FI-1/2A|D06FI-1/2B|D06FI-3/4A|D06FI-3/4B|D06FI-1A|D06FI-1B|D06FI-11/4A|D06FI-11/4B|D06FI-11/2A|D06FI-11/2B|D06FI-2A|D06FI-2B 典型應(yīng)用 Honeywell 減壓閥可設(shè)定和穩(wěn)定入戶水壓,節(jié)約用水量、保護(hù)用水設(shè)備免受水錘的影響。在它的特性范圍內(nèi),也可應(yīng)用于工業(yè)或商業(yè)領(lǐng)域。安裝了減壓閥后,不僅可以舒適**用水,避免超壓帶來(lái)的損害,也可節(jié)約用水量,減少資源浪費(fèi)。 ● 民用住宅 ● 公共建筑,酒店、醫(yī)院、商業(yè)區(qū)、學(xué)校、運(yùn)動(dòng)場(chǎng)館、 圖書館... ● 生活熱水系統(tǒng)工業(yè)應(yīng)用如:水,壓縮空氣

霍尼韋爾Honeywell D06F減壓閥
霍尼韋爾減壓閥工作原理
減壓閥的工作原理建立在兩個(gè)對(duì)應(yīng)的作用力相互平衡的基礎(chǔ)上——彈簧向下的作用力和隔膜向上的作用力。當(dāng)
打開(kāi)龍頭用水時(shí),出口壓力也即是隔膜壓力降低,彈簧的作用力大于作用在隔膜上的水的壓力,閥門打開(kāi)。出
口壓力下降直至隔膜和彈簧上的作用力再次平衡為止。
由于平衡式閥芯設(shè)計(jì), 無(wú)論閥門開(kāi)啟或者關(guān)閉,入口壓力都不會(huì)影響出口壓力。因此,入口壓力波動(dòng)不會(huì)造
成出口壓力的波動(dòng),出口壓力維持在一定范圍內(nèi)。
典型應(yīng)用
Honeywell 減壓閥可設(shè)定和穩(wěn)定入戶水壓,節(jié)約用水
量、保護(hù)用水設(shè)備免受水錘的影響。在它的特性范圍
內(nèi),也可應(yīng)用于工業(yè)或商業(yè)領(lǐng)域。安裝了減壓閥后,
不僅可以舒適**用水,避免超壓帶來(lái)的損害,也可
節(jié)約用水量,減少資源浪費(fèi)。
● 民用住宅
● 公共建筑,酒店、醫(yī)院、商業(yè)區(qū)、學(xué)校、運(yùn)動(dòng)場(chǎng)館、
圖書館...
● 生活熱水系統(tǒng)
● 預(yù)防超壓現(xiàn)象發(fā)生的水系統(tǒng),
● OEM 設(shè)備(洗碗機(jī)、凈水器、噴水機(jī)、洗車設(shè)備..)
● 工業(yè)應(yīng)用如:水,壓縮空氣、氮?dú)?br> 材質(zhì)
● 防脫鋅黃銅外殼
● 防脫鋅黃銅螺紋連接
● 高質(zhì)量合成材料閥芯
● 不銹鋼過(guò)濾網(wǎng)孔
● 高合成材料的彈簧閥帽
● 合成透明材質(zhì)或防脫鋅黃銅濾碗
● 鋼制調(diào)整彈簧
● 纖維增強(qiáng)NBR 隔膜
● NBR 密封
應(yīng)用范圍
介質(zhì)水,壓縮空氣、氮?dú)?br> (DIN EN 12502 標(biāo)準(zhǔn)范圍內(nèi))
入口壓力透明濾碗16bar
黃銅碗25bar
出口壓力1.5 ~ 6.0bar

APPLICATION
According EN 806-2 pressure reducing valves of this type
protect household water installations against excessive
pressure from the supply. They can also be used for
industrial or commercial applications within the range of
their specification.
By installing a pressure reducing valve, pressurisation
damage is avoided and water consumption is reduced.
The set pressure is also maintained constant, even when
there is wide inlet pressure fluctuation.
Reduction of the operating pressure and maintaining it at a

constant level minimizes flow noise in the installation.

APPROVALS
? DVGW
? WRAS (up to 23 °C)
SPECIAL FEATURES
? Inlet pressure balancing – no influence on outlet
pressure by fluctuating inlet pressure
? Up to size 11/4" approved by LGA for low noise, Group 1
without limitations
? The valve insert is of high-quality synthetic material
and can be fully exchanged
? The outlet pressure is set by turning the adjustment
knob
? The set pressure is directly indicated on the set point
scale
? The adjustment spring is not in contact with the
drinking water
? Integral fine filter
? Also available without fittings
? Conforms to BSEN 1567
? All materials are UBA conform
? ACS certified

TECHNICAL DATA
Note: Use the SM06T brass filter bowl, if the valve can be exposed to
UV radiation or solvent vapors.
Media
Medium: Drinking water
Connections/Sizes
Connection sizes: 1/2" - 2"
Nominal sizes: DN15 - DN50
Pressure values
Max. inlet pressure with clear
filter bowl:
16 bar
Max. inlet pressure with
brass filter bow:
25 bar
Outlet pressure: 1.5 - 6 bar
Preset outlet pressure: 3 bar
Min. pressure drop: 1 bar
Operating temperatures
Max. operating temperature
medium (10 bar/brass filter
bowl):
70 °C
Max. operating temperature
medium accord. to EN 1567:
30 °C

METHOD OF OPERATION
Spring loaded pressure reducing valves operate by means of
a force equalising system. The force of a diaphragm
operates against the force of an adjustment spring. If the
outlet pressure and therefore diaphragm force fall because
water is drawn, the then greater force of the spring causes
the valve to open. The outlet pressure then increases until
the forces between the diaphragm and the spring are equal
again.
The inlet pressure has no influence in either opening or
closing of the valve. Because of this, inlet pressure
fluctuation does not influence the outlet pressure, thus
providing inlet pressure balancing.
TRANSPORTATION AND STORAGE
Keep parts in their original packaging and unpack them
shortly before use.
The following parameters apply during transportation and
storage:

INSTALLATION GUIDELINES
Setup requirements
? Install in horizontal pipework with filter bowl
downwards
? Install shut-off valves
? The device downstream should be protected by means
of a safety valve (installed downstream of the pressure
reducing valve). In these cases the delivery pressure of
the pressure reducing valve shall be set to at least 20 %
below the response pressure of the pressure reliefvalve
according to EN 806-2
? The installation location should be protected against
frost and be easily accessible
? Pressure gauge can be read off easily
? With clear filter bowl, degree of contamination can
be easily seen
? Simplified maintenance and cleaning
? Install downstream of the filter or strainer
? Provide a straight section of pipework of at least five
times the nominal valve size after the pressure
reducing valve (in accordance with EN 806-2)
? Requires regular maintenance in accordance with
EN 806-5

Parameter Value
Environment: clean, dry and dust free
Min. ambient temperature: 5 °C
Max. ambient temperature: 55 °C
Min. ambient relative
humidity:
25 % *
Max. ambient relative
humidity:
85 % *